These are the calculations that show up most often on electrician exams, with the 2023 NEC sections to know. It’s a study aid, written in our own words. Your exam is answered from the code book itself, so practice finding each table.

Ohm’s law and power

Voltage drop

Continuous loads

A continuous load runs for 3 hours or more. Size the overcurrent device and conductors at no less than 125% of the continuous load plus 100% of the noncontinuous load (210.20 for branch circuits and 215.3 for feeders), unless the equipment is listed for 100% operation.

Conductor ampacity

Box fill (314.16)

Example: a box with four 12 AWG cables (8 insulated conductors, 4 grounds), one receptacle, and internal clamps: 8 + 1 (grounds) + 2 (device) + 1 (clamps) = 12 × 2.25 = 27 cubic inches.

Raceway fill (Chapter 9)

Motors (Article 430)

Dwelling load (standard method, Article 220)

  1. General lighting: 3 VA per square foot of living area.
  2. Add two 20 A small-appliance circuits at 1,500 VA each and one laundry circuit at 1,500 VA.
  3. Apply the lighting demand factors: first 3,000 VA at 100%, 3,001–120,000 VA at 35%, the rest at 25%.
  4. Add fixed appliances (75% demand for four or more, not counting ranges, dryers, space heating, or A/C), the dryer (5,000 VA or the nameplate, whichever is larger), cooking equipment from Table 220.55 (8 kW for one range of 12 kW or less), and the larger of heating or cooling.
  5. Divide by 240 V for the service current.

Grounding and bonding sizes

Transformers

Practice with 10 free questions Journeyman practice page

Section numbers refer to the 2023 NEC as adopted in Michigan by the Part 8 Michigan Electrical Code Rules. Always confirm values in your own code book. Exam facts: PSI candidate bulletin.

FAQ

What is the conduit fill limit for three or more conductors?

Chapter 9, Table 1 of the NEC limits fill to 40% of the raceway’s cross-sectional area for more than two conductors. It’s 53% for one conductor and 31% for two.

Do I use the motor nameplate or the NEC table for motor conductors?

For general motor applications, size conductors and short-circuit and ground-fault protection from the NEC full-load current tables (Table 430.248 for single-phase, Table 430.250 for three-phase), not the nameplate. Overload protection is based on the nameplate current.